Bolted Connection Design for Lattice Tower Members to IS 800 and IS 17740

How a bolted bracing end or leg splice is checked — bolt grade by IS 800 Table 1 with both amendments, bolt shear and bearing, the edge, end and pitch limits of Cl. 10.2, IS 17740's 12 mm minimum bolt, and the member's own net-section rupture and block shear — with one diagonal end worked by hand.

By Sutranet · A guide for practising structural engineers

Connections are where many tower designs fail a review. The member checks may pass, but a bolt is too close to an edge, the bolt grade is assumed rather than stated, or the end of an angle bolted through one leg was never checked for net-section rupture. IS 17740:2022 Cl. 13.1.1 sends bolted connections to IS 800:2007, and adds one rule of its own: the 12 mm minimum bolt of Cl. 13.1.2. This guide goes through the checks for a bolted bracing end in the order a checker would, and shows how SutranetTower carries them out.

1. What is checked at a bolted tower joint

A bolted bracing end has two sides, and both have to be checked:

In SutranetTower both are driven by one input: an optional connections block per section, with an entry for the diagonals, the horizontals, each redundant member tag, and the leg splice. The bolt line you declare there (hole diameter, number of bolts in line, pitch, end and edge distances) is the one source of hole geometry for the member check too. A section with no entry has no connection check, and its members' rupture and block shear are reported as not checked rather than passed.

The demand is the factored axial force from the envelope of all strength combinations, with tension and compression enveloped separately, so a tension-only limit state such as block shear is checked against the largest tension, not against whichever sign governs the member.

Partial safety factors are those of IS 800 Table 5, and IS 17740 Table 4 gives the same values: γm0 = 1.10 for yielding, γm1 = 1.25 for rupture, γmb = 1.25 for bearing-type bolts and γmw = 1.25 for shop welds. The field-weld value of 1.50 is not selectable.

2. Step 1: bolt grade and diameter

IS 800 Table 1 gives the minimum yield and ultimate strength of bolts by property class. Two amendments changed what it says:

Classfyb (MPa)fub (MPa)Note
4.6240400Yield values added by Amendment No. 2 (2024); the 2007 table had a dash
4.8320420
5.6300500
5.8400520
6.8480600
8.8, d ≤ 16 mm6408008.8 is split at 16 mm: an M20 8.8 bolt is 660 / 830, not 640 / 800
8.8, d > 16 mm660830
9.8720900
10.99401040
12.911001220

In the program you state the class ("bolt_grade": "8.8") and both strengths are read from this table at the bolt's diameter. You can instead state fub and fyb directly, but not both ways at once: two values for one strength would leave the program to pick one, so that is refused. If you state neither, 800 MPa is assumed and the report says so. A yield strength the check needs is never assumed: it comes from the class your fub names, or the run is refused.

IS 17740 Cl. 13.1.2 sets the bolt diameter at not less than 12 mm, and names 12, 16 and 20 mm as preferred sizes. The program checks the minimum on every connection type; the preferred sizes are a preference and are not checked.

3. Step 2: bolt shear (IS 800 Cl. 10.3.3)

The nominal shear capacity of one bolt is fub/√3 times its area in each shear plane. The program takes the area per plane as:

Vnsb = (fub / √3) · nplanes · A,   Vdsb = βlj · Vnsb / γmb

βlj is the long-joint reduction. When the length of the joint, lj = pitch × (n − 1), is more than 15d, βlj = 1.075 − 0.005 lj/d, kept between 0.75 and 1.0; otherwise it is 1.0. No other reduction on the bolt shear is applied.

The number of shear planes defaults to two (double shear). A single angle bolted to one gusset is in single shear, so state it. The fabrication one-liner on the report (for example 2 × M16 8.8 @ 50 c/c · single shear · 6 mm ply) is built from the values actually used, defaults included, so an unintended double shear shows there.

4. Step 3: bolt bearing (IS 800 Cl. 10.3.4)

Vnpb = 2.5 · kb · d · t · fu,   Vdpb = Vnpb / γmb
kb = min( e / 3d0,  p / 3d0 − 0.25,  fub / fu,  1.0 )

t is the ply thickness that governs bearing, fu its ultimate strength, e the end distance, p the pitch and d0 the hole diameter. The design value of one bolt is the lower of Vdsb and Vdpb, and the bolt group carries that times the number of bolts.

On tower bracing, with thin plies and short end distances, bearing usually governs, and the end distance is what sets it. If no end distance is given, the e/3d0 term cannot be evaluated; the program then leaves it out of kb, which over-states the bearing capacity, and so it reports the connection as failing detailing (Step 4) until the end distance is entered.

5. Step 4: detailing limits (IS 800 Cl. 10.2, IS 17740 Cl. 13.1.2)

The capacity equations assume a minimum geometry. The program checks:

RuleLimitClause
Minimum bolt diameter12 mmIS 17740 Cl. 13.1.2
Minimum end and edge distance1.7 d0 for sheared or hand-flame-cut edges; 1.5 d0 for rolled, machine-flame-cut, sawn or planed edgesIS 800 Cl. 10.2.4.2
Maximum edge distance12 t ε, ε = √(250/fy), t the thinner outer plyIS 800 Cl. 10.2.4.3
Minimum pitch2.5 d (nominal bolt diameter)IS 800 Cl. 10.2.2

The minimum end and edge distance depends on how the edge is made, and guessing it is unsafe either way: assuming 1.5 on a sheared edge passes a joint that does not comply, and assuming 1.7 on a rolled edge fails one that does. So the program has no default for the edge preparation. If you give distances without it, the minimum cannot be established and the joint reads DETAILING until the edge preparation is stated; an unrecognised value stops the run.

A detailing failure is reported as DETAILING, separately from OVERSTRESSED. A joint at 40 % utilisation with a bolt too close to an edge is not overstressed, and the fix is to move the bolt or change the plate, not to resize the member. Both verdicts fail the connection.

Two IS 800 limits are not checked: the maximum pitch of Cl. 10.2.3.1 (it differs between tension and compression members) and the reduced maximum edge distance for corrosive exposure.

6. Step 5: tension in the member (IS 17740 Cl. 11.1, IS 800 Cl. 6.3 and 6.4)

The design tension strength Td is the lowest of three values.

Gross-section yield

Tdg = Ag · fy / γm0

Net-section rupture of an angle bolted through one leg (IS 800 Cl. 6.3.3)

Tdn = 0.9 · Anc · fu / γm1 + β · Ago · fy / γm0
β = 1.4 − 0.076 · (w/t) · (fy/fu) · (bs/Lc),   0.7 ≤ β ≤ 0.9 · fuγm0 / (fyγm1)

Other end types, as the program treats them:

Block shear (IS 800 Cl. 6.4.1)

Tdb1 = Avg fy / (√3 γm0) + 0.9 Atn fu / γm1
Tdb2 = 0.9 Avn fu / (√3 γm1) + Atg fy / γm0
Tdb = min(Tdb1, Tdb2)

For one line of n bolts, with end distance e, pitch p, edge distance e' (bolt line to the free edge) and hole d0, the program takes the block as shear along the bolt line and tension across to the edge:

Block shear is checked on the member (an angle bolted through one leg) and on the connected element in the connection check. Without an end distance, an edge distance and (for two or more bolts) a pitch, it cannot be set up, and the report says it was not checked.

Net section of the connected plate

If you give the gross width of the connected plate, the connection check also takes its net section, 0.9 · (b − d0) · t · fu / γm1.

Eccentric bracing ends

A single angle whose bolt group lies beyond the centreline of the connected leg loses compression capacity under IS 17740 Cl. 10.4.4.2. That is a member check; it is covered in the member capacity guide, and its one input, the distance g from the heel to the bolt group, is entered in the same connections entry.

7. Leg splices: angle cover plates and pipe ring flanges

Angle legs

An angle leg is usually spliced with bolted lap or cover plates. The program checks it with the same limit states as a bracing end — bolt shear, bearing, plate net section, block shear and detailing — fed with the leg's own tension and compression, and in double shear unless you state otherwise. Where the angle ends are prepared for full contact in bearing, you may state that, and the compression fed to the splice is then halved, on the reading that IS 800 Cl. 10.8 requires the splice itself to carry at least 50 % of the compression; tension always takes the full force. Confirm that reading for your project before relying on it for a governing splice.

Pipe legs: the ring flange

A tube leg is usually spliced with a pair of welded ring flanges bolted on a pitch circle. The program checks:

8. What is not checked

9. Worked example: a diagonal end by hand

A single-angle diagonal bolted through one leg to a gusset, in single shear.

Inputs

ItemValue
DiagonalISA 65×65×6, E250 (fy 250, fu 410 MPa), Ag = 753 mm²
Bolts2 × M16, class 8.8 (fub 800 MPa at d ≤ 16 mm), threads in the shear plane
Hole d018 mm
Governing ply in bearing6 mm (angle leg and gusset both 6 mm, E250)
End distance e, pitch p, edge distance e'30 mm, 50 mm, 28 mm
EdgesRolled
Factored tension40 kN

Step 1: bolts

M16 is above the 12 mm minimum. Class 8.8 at 16 mm: fub = 800 MPa.

Step 2: bolt shear

Anb = 0.78 × π × 16² / 4 = 156.8 mm²

Vnsb = 800 / √3 × 1 × 156.8 = 72.4 kN. lj = 50 mm < 15d = 240 mm, so βlj = 1.0. Vdsb = 72.4 / 1.25 = 57.9 kN per bolt.

Step 3: bearing

kb = min(30/54, 50/54 − 0.25, 800/410, 1.0) = min(0.556, 0.676, 1.95, 1.0) = 0.556

Vnpb = 2.5 × 0.556 × 16 × 6 × 410 = 54.7 kN, Vdpb = 54.7 / 1.25 = 43.7 kN per bolt.

Bearing governs: the bolt group gives 2 × 43.7 = 87.5 kN.

Step 4: detailing

RuleLimitProvided
Bolt diameter≥ 12 mm16 mmOK
End distance, rolled≥ 1.5 × 18 = 27 mm30 mmOK
Edge distance, rolled≥ 27 mm28 mmOK
Maximum edge distance≤ 12 × 6 × 1.0 = 72 mm28 mmOK
Pitch≥ 2.5 × 16 = 40 mm50 mmOK

Step 5: tension in the angle

Gross yield: Tdg = 753 × 250 / 1.10 = 171.1 kN.

Rupture. The program splits the gross area into the connected leg, a·t = 65 × 6 = 390 mm², and the outstanding rest, Ago = 363 mm². Anc = 390 − 18 × 6 = 282 mm². w = 65 mm, w1 = 65 − 28 = 37 mm, bs = 65 + 37 − 6 = 96 mm, Lc = 50 mm.

β = 1.4 − 0.076 × (65/6) × (250/410) × (96/50) = 1.4 − 0.964 = 0.436, below the lower bound, so β = 0.7.

Tdn = 0.9 × 282 × 410 / 1.25 + 0.7 × 363 × 250 / 1.10 = 83.2 + 57.8 = 141.0 kN

Block shear: Avg = 6 × (30 + 50) = 480, Avn = 6 × (80 − 1.5 × 18) = 318, Atg = 6 × 28 = 168, Atn = 6 × (28 − 9) = 114 mm².

Tdb1 = 480 × 250 / (√3 × 1.10) + 0.9 × 114 × 410 / 1.25 = 63.0 + 33.7 = 96.6 kN
Tdb2 = 0.9 × 318 × 410 / (√3 × 1.25) + 168 × 250 / 1.10 = 54.2 + 38.2 = 92.4 kN

Td = min(171.1, 141.0, 92.4) = 92.4 kN, block shear governs the member.

Result

The end is limited by the bolts in bearing, 87.5 kN, just below the member's block shear of 92.4 kN. At 40 kN the bolt utilisation is 40 / 87.5 = 0.46, and the joint is OK. SutranetTower's connection and member checks give the same values.

Three changes show how sensitive this is:

10. Doing it in practice

A tower has a bracing end for every diagonal, horizontal and redundant group in every section, and the demand at each is a different envelope of a dozen combinations. In SutranetTower you describe each joint once in the section's connections block — bolt class and diameter, hole, number in line, pitch, end and edge distances, edge preparation, ply thickness and shear planes — and the program checks the bolts, the plies, the detailing and the member's rupture and block shear against the enveloped forces, reports OK, OVERSTRESSED or DETAILING for each, and prints the working and a fabrication one-liner for the member schedule.

Check the connections on your own tower.

Bolt shear and bearing, IS 800 Cl. 10.2 detailing, the IS 17740 minimum bolt and member rupture and block shear, against the full 3D analysis — free to start.

Try it free →

This guide is an engineering overview and is not a substitute for the standards. Clause numbers refer to IS 800:2007 with Amendments No. 1 (2012) and No. 2 (2024), and IS 17740:2022 with Amendment No. 1. Always design against the current published text and have connection details reviewed by a qualified structural engineer.